knestronX · LPDC platform
Battery inverter built from three modules
The Low-Power DC Platform (LPDC platform) connects the 230 VAC grid to batteries from 12 to 65 VDC. AC/DC converter, galvanic isolation, and bidirectional DC/DC converter are separate modules rated at 3.6 kW each. They can be freely combined and connected in parallel.
Energy flows in both directions: charging from the grid or a generator, discharging into the grid or into your own island grid.
3.6 kW
Rated power per module
5.8 kW
Peak power for 3 seconds
70 VDC
DC link below the 120 VDC limit for SELV and PELV
12–65 VDC
Adjustable battery voltage
The modules
One string, three tasks
Each module operates bidirectionally and is connected to the internal CAN bus. A higher-level master controls operating modes and setpoints.
Active front end between the 230 VAC grid and the 380 VDC DC link. As a PFC rectifier, it charges from the grid or a generator; as an inverter, it feeds back into the grid or forms its own grid.
Monitoring: overload, short circuit, temperature, undervoltage and overvoltage
Isolated, bidirectional DC/DC converter from 380 VDC to 70 VDC. It safely separates the high-voltage DC link from the extra-low-voltage side.
At 70 VDC, the bus stays below the 120 VDC limit and can be implemented as SELV or PELV.
Monitoring: overload, short circuit, temperature
Bidirectional DC/DC converter between the 70 VDC bus and a battery, PV module, or DC load. The output voltage is adjustable between 12 and 65 VDC.
Continuous power at 60 A battery current
Monitoring: overload, short circuit, temperature, undervoltage and overvoltage
Scaling
More power with more modules
The system can be expanded independently at three points. The same modules can form a small single-phase storage system or a three-phase system in the double-digit kilowatt range.
AC side
AFE in parallel
More power per phase or additional 230 VAC connections. Via the sync bus, three AFEs form a three-phase grid with 120° phase shift.
Isolation point
ISO parallel
Each additional ISO module increases the power transferred between the high-voltage and extra-low-voltage sides.
DC side
One DCD per battery
The 70 VDC bus runs as many DCDs as there are batteries, PV modules or DC loads connected, even at different voltages.
21.6 kW
Example calculation: two AFEs per phase, three phases. 6 × 3.6 kW add up to 21.6 kW rated power, three-phase.
Applications
Where the LPDC platform is used
Battery inverter
Charge and discharge storage on the 230 VAC grid. With 48 V batteries, two DCDs share the power; from 60 V upward, one is enough.
UPS for data centers
Online double-conversion UPS: one AFE rectifies the grid to 380 VDC, and a second AFE uses it to form the supply for the servers. The battery is connected to the DC link via ISO and DCD and takes over during a power outage without any switchover. Racks with 48 V DC are supplied directly by a DCD.
Generator Booster
The AFE operates in parallel with the generator and feeds in power from the battery. The storage covers load peaks, and the generator recharges it during low-load periods.
View the 27 kW configuration example
Emergency power supply
If the grid fails, the grid disconnect opens and the AFE forms the grid for the emergency circuit from the battery. Battery capacity determines the bridging time.
PV storage
PV modules connect directly to the 70 VDC bus via a DCD with MPPT and charge the battery without going through the AC grid.
Charging at a charging station
The AFE evaluates Control Pilot and Proximity Pilot. This allows the system to charge its battery at a wallbox or public charging station, for example as mobile storage.
Further applications
Battery test bench
The DCD charges and discharges battery modules from 12 to 65 V. The energy is fed back into the grid via the AFE instead of being dissipated as heat in load resistors.
Onboard power systems
For special-purpose vehicles, boats and motorhomes: shore power is turned into an onboard power system with battery buffer via galvanic isolation. Multiple DCDs supply different voltage levels.
Radio sites
Buffered 48 VDC supply for radio and network equipment. With PV via a DCD with MPPT, also at remote sites.
Peak shaving
The storage covers power peaks from machines or cooling systems, reducing the power drawn at the grid connection.
Second-life storage
Used battery packs with different voltages each operate on their own DCD on the shared 70 VDC bus.
Mobile power
For construction sites and events: the storage charges at a charging station and supplies power on site as an island grid, quietly and without exhaust fumes.
Configuration example
Generator support with 27 kW
A generator with 3 × 1.8 kW supplies loads whose peaks are far higher. Six strings of the LPDC platform raise the available power to 27 kW three-phase. A PV system additionally charges the storage.
Scroll the circuit diagram sideways to see all modules.
Why separate DC links? Each AFE operates between line conductor and neutral conductor. If the DC links of all phases were connected together, the phases would be interconnected via the AFEs. That is why each phase has its own 380 VDC DC link. Only after the galvanic isolation in the ISO module do all strings converge on the shared 70 VDC bus.
5.4 kW
Generator, 3 × 1.8 kW
+21.6 kW
from battery and PV via six AFEs, up to 32.4 kW for 3 seconds
27 kW
rated power, three-phase, for the loads
Bill of materials
Operating states
Low load
The generator covers the load. The AFEs use the surplus to charge the battery.
Load peak
The AFEs feed in power from the battery. The generator stays within its rated range.
Sun
The PV modules charge via the DCD with MPPT directly on the 70 VDC bus.
Generator off
The AFEs form the grid from battery and PV alone.
Sum of rated values. Sizing depends on load profile, generator and battery.
Interfaces
Networked via CAN
Installation space
Compact string
× 80 mm
× 100 mm
× 40 mm
Dimensions from the concept phase, subject to change during development.
Contact
Let's talk about your application
Tell us your grid connection, battery voltage and power requirement. We will suggest a suitable combination of modules.