Application · PV storage
PV storage with DC coupling at extra-low voltage
PV modules and battery each connect via a DCD to the shared 70 VDC bus. Solar power charges the battery directly, without the detour via the AC grid. Via ISO and AFE the bus connects to the 230 VAC grid or an island grid.
ISO and AFE for grid or island grid sit on the same bus. All voltages on the DC side stay below 120 VDC.
MPPT
in the DCD as an option
< 120 V
all DC voltages extra-low
3.6 kW
per DCD at 60 V
1 DCD
per PV array or battery
The task
Store solar power without double conversion
In AC-coupled systems a PV inverter converts solar power to AC, then a battery inverter rectifies it again. Every stage costs efficiency, which is especially noticeable in off-grid systems.
With modules at extra-low voltage, all DC lines also stay below 120 V. That simplifies installation and protection, for example on containers, masts or mobile systems.
Typical requirements
PV arrays at extra-low voltage up to 65 V
battery between 12 and 65 V
MPP tracking per PV array
grid connection or island operation
several arrays with different orientation
monitoring via Modbus
Our approach
PV and battery on the same bus
Each PV array gets a DCD with MPPT, each battery its own DCD. The 70 VDC bus connects everything, ISO and AFE link it to the AC side.
Sun
The DCD with MPPT gets the maximum from the PV array and feeds the bus. The battery DCD charges with the surplus.
Consumption
AFE and ISO supply AC loads from bus and battery, grid-parallel or as an island grid.
Several arrays
Arrays with different orientation or voltage work on their own DCDs and do not affect each other.
What sets it apart
Why knestronX
One conversion less
PV charges the battery directly at DC level.
Extra-low voltage on the DC side
PV, bus and battery stay below 120 VDC.
One MPPT per array
Shading or different orientation of one array does not disturb the others.
Grid or island
The AFE works grid-parallel or forms its own grid.
Combinable
With generator, backup power or peak shaving from the same modules.
Open interfaces
CAN to the BMS, Modbus for monitoring.
Key data
Specifications at a glance
Building blocks used
Fields of use
FAQ
Questions from practice
Which PV modules fit?
The DCD works up to 65 V. The PV array is wired so that its voltage stays within this range even in cold weather, usually with modules in parallel rather than long strings.
How much PV power can one DCD handle?
The DCD is rated for 60 A. At 60 V that is 3.6 kW, at 40 V about 2.4 kW. Larger arrays get several DCDs.
And for large PV plants up to 1500 V?
For that there is PV direct coupling on the HPDC platform with 250 kW per converter.
Related applications
Buffered 48 VDC for radio and network equipment
Buffered 48 VDC supply for radio and network equipment, with PV via MPPT even at remote sites.
Backup power from the battery, single- or three-phase
When the grid fails, the AFE forms the grid for the backup circuit from the battery, single- or three-phase.
Solar power straight into high-voltage storage
PV strings charge 1500 V storage directly, with MPPT and buck-boost operation.
Contact
Let's talk about your application
Tell us PV power and module layout, battery voltage, loads and whether the system runs grid-parallel or off-grid.
KNESTEL Technologie & Elektronik GmbH
Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de
Technical data: status prototype phase. Subject to change. Design and sizing depend on the individual project.