LPDC platform Status: Prototype phase

Application · PV storage

PV storage with DC coupling at extra-low voltage

PV modules and battery each connect via a DCD to the shared 70 VDC bus. Solar power charges the battery directly, without the detour via the AC grid. Via ISO and AFE the bus connects to the 230 VAC grid or an island grid.

PV modules up to 65 VDC
DCD MPPT
70 VDC bus
DCD battery
12–65 V
Battery e.g. 48 V

ISO and AFE for grid or island grid sit on the same bus. All voltages on the DC side stay below 120 VDC.

MPPT

in the DCD as an option

< 120 V

all DC voltages extra-low

3.6 kW

per DCD at 60 V

1 DCD

per PV array or battery

The task

Store solar power without double conversion

In AC-coupled systems a PV inverter converts solar power to AC, then a battery inverter rectifies it again. Every stage costs efficiency, which is especially noticeable in off-grid systems.

With modules at extra-low voltage, all DC lines also stay below 120 V. That simplifies installation and protection, for example on containers, masts or mobile systems.

Typical requirements

PV arrays at extra-low voltage up to 65 V

battery between 12 and 65 V

MPP tracking per PV array

grid connection or island operation

several arrays with different orientation

monitoring via Modbus

Our approach

PV and battery on the same bus

Each PV array gets a DCD with MPPT, each battery its own DCD. The 70 VDC bus connects everything, ISO and AFE link it to the AC side.

01

Sun

The DCD with MPPT gets the maximum from the PV array and feeds the bus. The battery DCD charges with the surplus.

02

Consumption

AFE and ISO supply AC loads from bus and battery, grid-parallel or as an island grid.

03

Several arrays

Arrays with different orientation or voltage work on their own DCDs and do not affect each other.

What sets it apart

Why knestronX

One conversion less

PV charges the battery directly at DC level.

Extra-low voltage on the DC side

PV, bus and battery stay below 120 VDC.

One MPPT per array

Shading or different orientation of one array does not disturb the others.

Grid or island

The AFE works grid-parallel or forms its own grid.

Combinable

With generator, backup power or peak shaving from the same modules.

Open interfaces

CAN to the BMS, Modbus for monitoring.

Key data

Specifications at a glance

Parameter Value
DCD with MPPT PV input up to 65 VDC, 60 A continuous
DCD 70 VDC to 12–65 VDC, 60 A continuous, 105 A for 3 s
ISO 380 to 70 VDC, 3.6 kW, insulation strength 2 or 4 kV
AFE 230 VAC ±10 %, 3.6 kW, 16 A; 5.4 kW for 3 s
Power per DCD voltage-dependent, 3.6 kW at 60 V and 60 A
Interfaces internal CAN, CAN to BMS, Modbus optional, sync bus for AFE

Building blocks used

DCD with MPPT PV array on the 70 VDC bus
DCD battery charge and discharge
ISO galvanic isolation 380 to 70 VDC
AFE AC/DC conversion, PFC or grid-forming

Fields of use

off-grid systems and remote sites containers and equipment buildings radio and measurement sites mobile systems agricultural buildings

FAQ

Questions from practice

Which PV modules fit?

The DCD works up to 65 V. The PV array is wired so that its voltage stays within this range even in cold weather, usually with modules in parallel rather than long strings.

How much PV power can one DCD handle?

The DCD is rated for 60 A. At 60 V that is 3.6 kW, at 40 V about 2.4 kW. Larger arrays get several DCDs.

And for large PV plants up to 1500 V?

For that there is PV direct coupling on the HPDC platform with 250 kW per converter.

Contact

Let's talk about your application

Tell us PV power and module layout, battery voltage, loads and whether the system runs grid-parallel or off-grid.

KNESTEL Technologie & Elektronik GmbH

Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de

Technical data: status prototype phase. Subject to change. Design and sizing depend on the individual project.