Application · Generator booster
More power from a small generator
Generators are usually sized for the highest load peak and then run at part load most of the time. With the LPDC platform, a generator sized for the average load is enough. The battery supplies the peaks, the generator recharges it in quiet phases.
The AFEs run in parallel with the generator on the same three-phase grid and are synchronised via the sync bus.
27 kW
rated three-phase power in the example
5.4 kW
generator power, 3 × 1.8 kW
32.4 kW
for 3 seconds
120°
three AFEs form a three-phase grid
The task
The generator is too big for everyday use
Construction sites, events and remote locations have load profiles with short, high peaks: compressors, pumps, tools, refrigeration. If the generator is sized for these, it runs far below rated load most of the time. Consumption per kilowatt hour rises, and diesel engines tend to soot up at part load.
A storage system that takes over the peaks allows a much smaller generator. This needs power electronics that feed into the grid in parallel with the generator and can also form a grid without it.
Typical requirements
load peaks far above continuous load
three-phase loads
operation without generator in quiet phases
integration of PV modules
extra-low-voltage battery, e.g. 48 V LiFePO4
expansion as demand grows
Our approach
Two strings per phase, one battery on a shared bus
In the configuration example, six strings of AFE and ISO work together, two per phase. Each phase has its own 380 VDC link. Only behind the galvanic isolation do all strings meet on the shared 70 VDC bus.
Low load: generator charges
The generator covers the load. The AFEs use the surplus to charge the battery.
Load peak: battery assists
The AFEs feed from the battery into the grid. The generator stays within its rated range.
Sun, and generator off
PV modules charge directly on the 70 VDC bus via a DCD with MPPT. With the generator off, the AFEs form the grid from battery and PV alone.
What sets it apart
Why knestronX
Small generator, same power
In the example, a 5.4 kW generator together with the battery supplies 27 kW three-phase to the loads.
Generator at a good operating point
The generator runs steadily close to its rated load, which lowers consumption per kilowatt hour.
Quiet phases without generator
At low load the AFEs form the grid from battery and PV, without noise and exhaust.
Separate DC links per phase
Each AFE works between line and neutral. Separate DC links prevent the phases from being connected through the modules.
PV without detour
The DCD with MPPT charges the battery directly at DC level. No conversion via the AC grid.
Expandable per phase
More AFEs per phase, more ISOs, more DCDs: each point can be expanded independently.
Key data
Specifications at a glance
Building blocks used
Fields of use
FAQ
Questions from practice
Which battery fits?
Any battery between 12 and 65 V that communicates with the DCD via CAN. The example uses a 48 V battery, such as LiFePO4. Capacity depends on load profile and the desired runtime without generator.
What happens if the generator fails?
The AFEs then operate grid-forming and supply the loads from battery and PV. Runtime is set by battery capacity.
Can it be smaller?
Yes. One string per phase already gives 16.2 kW three-phase with a 5.4 kW generator. Single-phase, the platform starts with one string and 3.6 kW.
Related applications
Mobile storage for construction sites and events
The storage charges at a charging station and supplies on site as an island grid, quietly and without exhaust.
Shave load peaks, relieve the grid connection
Storage covers peaks from machines or refrigeration and lowers the demand at the grid connection.
Backup power from the battery, single- or three-phase
When the grid fails, the AFE forms the grid for the backup circuit from the battery, single- or three-phase.
Contact
Let's talk about your application
Tell us your generator power, load profile with peaks and duration, battery voltage and desired runtime without generator.
KNESTEL Technologie & Elektronik GmbH
Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de
Technical data: status prototype phase. Subject to change. Design and sizing depend on the individual project.