LPDC platform Status: Prototype phase

Application · UPS for data centres

Online UPS with double conversion for servers and equipment rooms

Servers, network equipment and control rooms must not drop out for a moment when the grid fails. The LPDC platform forms an online UPS: the loads always hang on the inverter, the battery always on the DC link. Nothing switches over when the grid fails.

230 VAC grid
AFE rectifier
380 VDC
AFE grid-forming
230 VAC
Servers uninterrupted

The battery connects to the 380 VDC link via ISO and DCD and is always engaged. Another DCD supplies 48 VDC racks directly.

0

switchover events on grid failure

48 VDC

rack supply directly via DCD

3.6 kW

per string, expandable in parallel

10.8 kW

three-phase with three strings

The task

No switchover, no interruption

Many small UPS units work offline or line-interactive and only switch to battery when the grid fails. For sensitive IT that is a risk. Online UPS with double conversion avoids it, but is usually built as a closed box without room for adaptation.

At the same time the share of equipment with 48 VDC supply is growing. A classic UPS first generates AC for these racks and then rectifies it again.

Typical requirements

uninterrupted supply without switchover

extra-low-voltage battery

48 VDC outputs for racks and network equipment

single- or three-phase outputs

remote monitoring via Modbus

modular expansion

Our approach

Double conversion from standard modules

Two AFEs and one string of ISO and DCD are enough for a single-phase online UPS. Three strings with synchronised AFEs give a three-phase output.

01

Rectify

The first AFE rectifies the grid to 380 VDC as a PFC rectifier and supplies the DC link.

02

Form the grid

The second AFE forms the grid for the servers from the DC link. It always runs, even with the grid intact.

03

Battery engaged

The battery connects to the DC link via ISO and DCD. If the grid fails, it keeps supplying the DC link. The second AFE notices nothing.

What sets it apart

Why knestronX

No switchover

The loads hang permanently on the grid-forming AFE. A grid failure only changes where the DC link draws its energy.

48 V without detour

A DCD supplies 48 VDC racks directly from the extra-low-voltage bus, without inverter and power supply in between.

Extra-low-voltage battery

The battery sits behind the galvanic isolation in the 12 to 65 V range.

Modular, not a black box

Power, battery voltage and outputs are assembled from modules and parameterised.

Monitoring

CAN to the BMS, Modbus for DTU and monitoring.

For integrators

The platform is for manufacturers and integrators building their own UPS systems.

Key data

Specifications at a glance

Parameter Value
AFE 230 VAC ±10 %, 3.6 kW, 16 A; 5.4 kW for 3 s
AFE grid-forming 230 VAC, 3.6 kW, 5.4 kW for 3 s
ISO 380 to 70 VDC, 3.6 kW, insulation strength 2 or 4 kV
DCD 70 VDC to 12–65 VDC, 60 A continuous, 105 A for 3 s
Three-phase 3 strings, AFEs synchronised via sync bus
Interfaces internal CAN, CAN to BMS, Modbus optional, sync bus for AFE

Building blocks used

AFE (2 per string) rectifier and grid-forming inverter
ISO galvanic isolation 380 to 70 VDC
DCD battery and 48 V outputs
Master operating modes and setpoints via CAN

Fields of use

edge data centres and server rooms network and equipment rooms control rooms and critical-infrastructure IT telecommunications equipment lab and measurement equipment

FAQ

Questions from practice

What is the difference from backup power?

With backup power, a grid disconnect opens when the grid fails, and only then does the AFE form the grid. With the online UPS the loads always hang on the grid-forming AFE, nothing switches over.

What power is possible?

One string delivers 3.6 kW single-phase, three strings 10.8 kW three-phase. More AFEs per phase increase power.

And for large AI data centres?

There, distribution moves to 800 VDC. The AI data centre page shows how HPDC and LPDC work together.

Contact

Let's talk about your application

Tell us power, outputs (230 VAC, 48 VDC), desired bridging time and battery voltage.

KNESTEL Technologie & Elektronik GmbH

Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de

Technical data: status prototype phase. Subject to change. Design and sizing depend on the individual project.