HPDC + LPDC Status: Solution concept

Application · AI data centre

800 VDC in the data centre: from the bus to extra-low voltage

AI racks with several hundred kilowatts are moving power distribution to DC. One megawatt at 54 V means about 18.5 kA, at 800 V it is 1.25 kA. knestronX splits the tasks between two platforms: HPDC for the 800 V level and storage, LPDC for extra-low voltage.

3~ AC grid, MV transformer
AFE central
800 VDC bus
ITS HPDC, isolated
50–70 VDC
DCD LPDC
48 / 24 / 12 V
Loads rack, infrastructure

Red: high-voltage level with HPDC. Green: extra-low-voltage level with LPDC. The galvanic isolation sits in the HPDC module.

800 VDC

central bus

250 kW

per HPDC module

12–65 V

adjustable per LPDC DCD

< 120 V

extra-low-voltage bus for SELV/PELV

The task

Too much current on the low-voltage side

Conventional data centres distribute AC and convert several times on the way to the processor. As rack power rises, currents, conductor cross-sections and conversion losses become the bottleneck. 800 VDC architectures move distribution to a higher voltage and lower the currents.

This creates new tasks: central rectification, storage directly on the DC bus, galvanically isolated conversion from 800 V to an intermediate bus around 50 V, and still auxiliary voltages for cooling, control, networking and monitoring. AI loads change their power draw quickly, and the supply has to follow.

Typical requirements

central AC/DC conversion to 800 VDC

battery storage on the DC bus for load steps and ride-through

galvanically isolated conversion to 48 to 54 VDC

auxiliary voltages 12 and 24 VDC, partly 230 VAC

insulation coordination and protection at 800 VDC

monitoring and control via digital interfaces

Our approach

Two platforms, clear division of tasks

HPDC works where power and voltage are high. LPDC takes over the extra-low voltages behind the galvanic isolation. Both platforms are modular and can be expanded independently.

01

HPDC: 800 V bus and storage

An active front end rectifies centrally. ITS modules with 250 kW connect battery storage bidirectionally to the bus and absorb load steps with a current rise time below 1 ms. With the 800 VDC input option the modules work directly on the bus, without a balancer.

02

HPDC: from 800 V to extra-low voltage

ITS modules with 800 VDC input and low-voltage option convert the 800 V bus, galvanically isolated, to an intermediate bus of 50 to 70 VDC. The isolation between high voltage and extra-low voltage thus sits in the module.

03

LPDC: everything below

On the intermediate bus, LPDC DCDs supply 48 V battery modules and 24 and 12 V for pumps, fans, controls and networking. Where AC is needed, an AFE forms 230 VAC, as an online UPS if required.

What sets it apart

Why knestronX

One platform family across all levels

Same communication paths, same supplier from 800 V down to 12 V.

Storage without AC detour

Batteries connect directly to the DC bus via bidirectional ITS. Additional AC/DC and DC/AC stages are eliminated.

Isolation in the right place

Galvanic isolation in the HPDC module. Everything behind it stays below 120 VDC and can be designed as SELV or PELV.

SiC on the high-voltage side

Over 98 % efficiency per HPDC module. With megawatt loads, every percent counts as waste heat.

Digitally monitored

EtherCAT and CAN in HPDC, CAN and Modbus in LPDC. Status data for diagnostics and load management.

Migration path

Existing AC distribution stays. Individual high-density zones get an 800 VDC bus, others follow.

Key data

Specifications at a glance

Parameter HPDC LPDC
Role 800 V bus, storage coupling, conversion to intermediate bus intermediate bus, 48 V batteries, auxiliary voltages, 230 VAC
Power per module 250 kW, 325 kW for 5 s 3.6 kW, 5.8 kW for 3 s
Voltages input 650–750 VDC (800 VDC optional, without balancer), with balancer up to 1500 VDC; output up to 1400 VDC, low-voltage option 25–100 VDC bus 70 VDC; outputs 12–65 VDC; AC 230 VAC
Currents ±700 A parallel, ±350 A series per module 60 A per DCD, 105 A for 3 s
Isolation resonant transformer, 5.2 kV AC ISO module 2 kV or 4 kV
Efficiency > 98 % status prototype phase
Communication EtherCAT, MLVDS, CAN CAN, Modbus

Building blocks used

HPDC · AFE central rectification to 800 VDC
HPDC · ITS (800 VDC option) storage coupling and conversion to 50–70 VDC
LPDC · DCD 48 / 24 / 12 V, BBU connection
LPDC · AFE 230 VAC for infrastructure, online UPS

Fields of use

AI and HPC data centres high-density zones in colocation data centres edge data centres battery storage and BBUs in data centres research computers and test environments

FAQ

Questions from practice

Does knestronX replace the power supplies in the rack?

No. Point-of-load supply for GPUs and processors stays with specialised converters on the board. knestronX addresses the bus, storage, the intermediate bus and the auxiliary voltages.

Why two platforms instead of one?

The requirements of 800 V with hundreds of kilowatts and of 12 V with a few kilowatts are too different for one module. Each platform is designed for its level, both use open interfaces.

Is the system available off the shelf?

The combination is a solution concept. The HPDC modules are available, the LPDC modules are in the prototype phase. We design the specific architecture with planners and operators per project.

Contact

Let's talk about your application

Tell us rack power and count, planned distribution voltage, storage concept and required auxiliary voltages. We will show which levels knestronX can cover.

KNESTEL Technologie & Elektronik GmbH

Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de

Technical data: status concept. Subject to change. Design and sizing depend on the individual project.