Application · Battery inverter
Battery inverter for storage from 12 to 65 V
Battery manufacturers and integrators building storage systems need power electronics between grid and battery. The LPDC platform provides it as three modules of 3.6 kW each: single-phase from one string, three-phase with three synchronised strings.
Energy flows both ways: charging from the grid, discharging into the grid or into a separate island grid.
3.6 kW
single-phase at 230 VAC
10.8 kW
three-phase with three strings
12–65 V
adjustable battery voltage
2 / 4 kV
insulation strength of the isolation stage
The task
Good batteries, but no power electronics of their own
Companies that build or integrate batteries want to offer storage without developing an inverter themselves. Off-the-shelf inverters rarely fit: wrong battery voltage, no communication with their own BMS, no way to build the device under their own brand.
Then there is the battery voltage. Many storage systems work at 24, 48 or 51.2 V, in the extra-low-voltage range. The power electronics must isolate this voltage safely from the 230 VAC grid.
Typical requirements
batteries between 12 and 65 V
single- or three-phase grid connection
charge and discharge with one device
communication with your own BMS
build under your own brand
expansion as storage grows
Our approach
One string of three modules
AFE, ISO and DCD form one string. The AFE works at the grid, the ISO module isolates galvanically, the DCD controls battery current and voltage.
Charging
The AFE rectifies 230 VAC to 380 VDC as a PFC rectifier. Its input current can be limited to 6, 10 or 16 A so the storage does not overload the building fuse.
Discharging
As an inverter the AFE feeds from the battery back into the grid or forms its own grid. With 48 V batteries two DCDs share the 3.6 kW, from 60 V one is enough.
Three-phase and larger
Three strings with AFEs synchronised via the sync bus give 10.8 kW three-phase with 120° phase shift. More AFEs per phase increase power further.
What sets it apart
Why knestronX
Power electronics without in-house development
Battery manufacturers combine the modules and parameterise them for their product.
Extra-low-voltage battery side
Batteries up to 65 V are easier to handle, transport and service than high-voltage packs.
Matched to battery voltage
60 A continuous per DCD: 720 W at 12 V, 2.88 kW at 48 V, 3.6 kW at 60 V.
BMS connection
The DCD talks to the battery management system via CAN. Modbus for DTU and monitoring is available as an option.
Expandable step by step
AC side, isolation stage and battery side can be expanded independently.
Adapted for volume
For larger quantities we adapt voltages, power ratings and interfaces.
Key data
Specifications at a glance
Building blocks used
Fields of use
FAQ
Questions from practice
How many DCDs do I need for 3.6 kW?
That depends on battery voltage, because each DCD delivers 60 A continuously. At 60 V one is enough, at 48 V two, at 24 V three.
May the storage feed into the public grid?
Grid-parallel operation follows each country's connection rules, in Germany VDE-AR-N 4105. We plan the certifications with you as part of product development. The modules are at prototype stage.
Can the storage be expanded later?
Yes. More DCDs for additional batteries, more ISOs for more transfer power and more AFEs for more power per phase.
Related applications
Backup power from the battery, single- or three-phase
When the grid fails, the AFE forms the grid for the backup circuit from the battery, single- or three-phase.
PV storage with DC coupling at extra-low voltage
PV modules charge directly on the 70 VDC bus via a DCD with MPPT, without a detour via the AC grid.
Shave load peaks, relieve the grid connection
Storage covers peaks from machines or refrigeration and lowers the demand at the grid connection.
Contact
Let's talk about your application