HPDC platform Status: Engineered on request

Application · Electrolysis and Power-to-X

Direct current for electrolysers and Power-to-X

An electrolyser is a large DC load. How much hydrogen it produces depends on the current. The HPDC platform supplies stacks with controlled direct current, up to 700 A per module in parallel, galvanically isolated and scalable in 250 kW steps.

Source grid, PV, DC grid
up to 1500 VDC
Balancer optional
650–800 VDC
BRW isolation
TSB current control
up to 700 A
Stack electrolyser

Typical topology: balancer + BRW + 2L-TSB. Without balancer the modules work at 650–750 VDC, optionally at 800 VDC.

700 A

per module in parallel

250 kW

per module, up to the MW range

< 0.1 %

ripple of full scale

> 98 %

efficiency per module

The task

Hydrogen is a matter of current

Electrolysers need high currents at voltages of a few hundred volts. Classic thyristor rectifiers are robust but have a poor power factor and high ripple at part load. With renewable power, however, an electrolyser often runs at part load.

When power from PV or a DC grid is used directly, a conversion stage via the AC grid can be dropped. The supply must then handle high DC input voltages.

Typical requirements

high currents per stack

precise current control even at part load

low ripple

galvanic isolation between source and stack

input from grid, PV or DC grid

scaling into the MW range

Our approach

One module per stack, combinable

Each module controls the current of its stack. For large stacks several modules work in parallel, for high stack voltages in series.

01

Control the current

The TSBs work in current control with a rise time below 1 ms and ripple below 0.1 % of full scale.

02

Isolated per stack

The BRWs isolate galvanically. Stacks can have their own potentials and run independently.

03

Directly on DC

With a balancer the modules handle DC inputs up to 1500 VDC, for example from a PV field or DC grid. On the grid, an AFE does the rectification.

What sets it apart

Why knestronX

High currents

700 A per module in parallel, several modules for larger stacks.

Clean supply

Ripple below 0.1 % of full scale.

Part-load capable

Controlled current over the entire operating range.

Redundant

If one module fails, the others keep running.

DC coupling

Input up to 1500 VDC with balancer, without detour via AC.

Measurement with PAM

Precise current and voltage measurement for balancing and control.

Key data

Specifications at a glance

Parameter Value
Topology balancer + BRW + 2L-TSB
Module KNT ITS SC 1, SiC
Input 650–750 VDC (800 VDC optional); with balancer up to 1500 VDC
Output parallel up to approx. 684 VDC / ±700 A, series up to 1400 VDC / ±350 A
Power 250 kW per module
Dynamics current rise < 1 ms
Ripple < 0.1 % FS on resistive load
Cooling water 18–22 °C
Communication EtherCAT, CAN, Modbus

Building blocks used

TSB current control per stack
BRW galvanic isolation
Balancer DC input up to 1500 VDC
PAM precision measurement

Fields of use

PEM and AEM electrolysis Power-to-X pilot plants PV-coupled electrolysis on-site hydrogen production at industrial sites research plants

FAQ

Questions from practice

How much current can the system deliver?

700 A per module in parallel. Several modules give correspondingly more, power grows in 250 kW steps.

Can the electrolyser run directly on PV?

With a balancer the modules handle PV voltages up to 1500 VDC. MPP control is handled by a higher-level controller or an upstream stage, see PV direct coupling.

And for test fields?

For electrolyser and fuel cell test fields with source and sink there is a dedicated application page.

Contact

Let's talk about your application

Tell us stack voltage and current, number of stacks, energy source and desired total power.

KNESTEL Technologie & Elektronik GmbH

Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de

Technical data: status 2026. Subject to change. Design and sizing depend on the individual project.