Application · AI data centre
800 VDC in the data centre: from the bus to extra-low voltage
AI racks with several hundred kilowatts are moving power distribution to DC. One megawatt at 54 V means about 18.5 kA, at 800 V it is 1.25 kA. knestronX splits the tasks between two platforms: HPDC for the 800 V level and storage, LPDC for extra-low voltage.
Red: high-voltage level with HPDC. Green: extra-low-voltage level with LPDC. The galvanic isolation sits in the HPDC module.
800 VDC
central bus
250 kW
per HPDC module
12–65 V
adjustable per LPDC DCD
< 120 V
extra-low-voltage bus for SELV/PELV
The task
Too much current on the low-voltage side
Conventional data centres distribute AC and convert several times on the way to the processor. As rack power rises, currents, conductor cross-sections and conversion losses become the bottleneck. 800 VDC architectures move distribution to a higher voltage and lower the currents.
This creates new tasks: central rectification, storage directly on the DC bus, galvanically isolated conversion from 800 V to an intermediate bus around 50 V, and still auxiliary voltages for cooling, control, networking and monitoring. AI loads change their power draw quickly, and the supply has to follow.
Typical requirements
central AC/DC conversion to 800 VDC
battery storage on the DC bus for load steps and ride-through
galvanically isolated conversion to 48 to 54 VDC
auxiliary voltages 12 and 24 VDC, partly 230 VAC
insulation coordination and protection at 800 VDC
monitoring and control via digital interfaces
Our approach
Two platforms, clear division of tasks
HPDC works where power and voltage are high. LPDC takes over the extra-low voltages behind the galvanic isolation. Both platforms are modular and can be expanded independently.
HPDC: 800 V bus and storage
An active front end rectifies centrally. ITS modules with 250 kW connect battery storage bidirectionally to the bus and absorb load steps with a current rise time below 1 ms. With the 800 VDC input option the modules work directly on the bus, without a balancer.
HPDC: from 800 V to extra-low voltage
ITS modules with 800 VDC input and low-voltage option convert the 800 V bus, galvanically isolated, to an intermediate bus of 50 to 70 VDC. The isolation between high voltage and extra-low voltage thus sits in the module.
LPDC: everything below
On the intermediate bus, LPDC DCDs supply 48 V battery modules and 24 and 12 V for pumps, fans, controls and networking. Where AC is needed, an AFE forms 230 VAC, as an online UPS if required.
What sets it apart
Why knestronX
One platform family across all levels
Same communication paths, same supplier from 800 V down to 12 V.
Storage without AC detour
Batteries connect directly to the DC bus via bidirectional ITS. Additional AC/DC and DC/AC stages are eliminated.
Isolation in the right place
Galvanic isolation in the HPDC module. Everything behind it stays below 120 VDC and can be designed as SELV or PELV.
SiC on the high-voltage side
Over 98 % efficiency per HPDC module. With megawatt loads, every percent counts as waste heat.
Digitally monitored
EtherCAT and CAN in HPDC, CAN and Modbus in LPDC. Status data for diagnostics and load management.
Migration path
Existing AC distribution stays. Individual high-density zones get an 800 VDC bus, others follow.
Key data
Specifications at a glance
Building blocks used
Fields of use
FAQ
Questions from practice
Does knestronX replace the power supplies in the rack?
No. Point-of-load supply for GPUs and processors stays with specialised converters on the board. knestronX addresses the bus, storage, the intermediate bus and the auxiliary voltages.
Why two platforms instead of one?
The requirements of 800 V with hundreds of kilowatts and of 12 V with a few kilowatts are too different for one module. Each platform is designed for its level, both use open interfaces.
Is the system available off the shelf?
The combination is a solution concept. The HPDC modules are available, the LPDC modules are in the prototype phase. We design the specific architecture with planners and operators per project.
Related applications
Online UPS with double conversion for servers and equipment rooms
Online UPS with double conversion, battery on the DC link. A DCD supplies 48 V racks directly.
Couple storage and DC grids bidirectionally
Bidirectional coupling of storage and DC grids, for example in smart grids.
Battery inverter for storage from 12 to 65 V
Charge and discharge storage at the 230 VAC grid. At 48 V two DCDs share the power, from 60 V one is enough.
Contact
Let's talk about your application
Tell us rack power and count, planned distribution voltage, storage concept and required auxiliary voltages. We will show which levels knestronX can cover.
KNESTEL Technologie & Elektronik GmbH
Osterwalder Strasse 12
87496 Hopferbach, Germany
Phone +49 8372 708-0
vertrieb@knestel.de
Technical data: status concept. Subject to change. Design and sizing depend on the individual project.